400 KVA Diesel Generator

Generator Specifications:

Genset Manufacturer

Greaves Power

Genset Rating

Prime Power

Genset Output ( KVA / KWe)

400 / 400

Genset Model

GPWII–400

Engine Model

12V14TAG23

Engine Type

TCAC

No. of Cylinders / Cylinder arrangement

12 / V- type

Displacement (L)

16.8

Bore & Stroke (mm)

115 X 135

Compression ratio

17

Rated RPM

1500

Governor: Type /Class of Governing

Electronic/G3

Over speed trip (rpm)

1650

Air cleaner type / Qty

Dry / 02

Exhaust system

Maximum allowable back pressure, kPa

7

Compare
Product ID: 2627 Category:

 

400 kva specsheet- Download

Diesel Generator Set Specifications Sheet- 400 kVA

Alternator Specification:

Voltage

380-440V

Frequency

50Hz

Current @ 0.8PF (Amps)

556.5

Type

4 Pole , Rotating field

Exciter Type

Brushless (Permanent magnet optional)

Leads: Quantity , type

6, fixed.

12, re connectable (Optional)

Voltage regulator

Solid State

Insulation

Class H ,

Temperature rise

125 Deg. C (Class H)

Bearing: Quantity , type

1,Sealed

Coupling

Flexible disc closed coupled

Voltage regulation : No load to full load

2 Phase sensing,±1%

One step load acceptance

100% of rating

Unbalance load capability

25% of rated current

image

Generator Specifications:

Genset Manufacturer

Greaves Power

Genset Rating

Prime Power

Genset Output ( KVA / KWe)

400 / 400

Genset Model

GPWII–400

Engine Model

12V14TAG23

Engine Type

TCAC

No. of Cylinders / Cylinder arrangement

12 / V- type

Displacement (L)

16.8

Bore & Stroke (mm)

115 X 135

Compression ratio

17

Rated RPM

1500

Governor: Type /Class of Governing

Electronic/G3

Over speed trip (rpm)

1650

Air cleaner type / Qty

Dry / 02

Exhaust system

Maximum allowable back pressure, kPa

7

Standard scope of supply:

Engine Electrical system:

Charging alternator Voltage / Current (DC)

24V / 44Amps

Starter Motor rated voltage (DC)

24

Battery Voltage (DC) / Capacity (AH)

24V, 2*180AH

Engine with direct injection, water cooled engine,12 cylinder, V-type, 4 stroke, rated at 1500 RPM, conforming to ISO 3046 / BS 5514 has the following specifications:

  • Mechanical FIP
  • Electronic governor
  • Turbocharger, pulse tuned exhaust manifold, stainless steel exhaust flexible connection
  • Radiator Cooled, with turbocharged after cooled-Plate type lube oil cooler-Filter –fuel, lube oil

    Fuel System:

    Recommended Fuel

    HSD

    Fuel tank capacity ( Ltr)

    990

    Fuel consumption – LPH at % load

    100%

    88.8

    75%

    66.6

    50%

    48.9

    25%

    26.1

  • Dry type replaceable paper element air cleaner
  • Flywheel housing and flywheel to suit single bearing alternator
  • Starting motor – Electric, battery charging alternator
  • First fill lube oil and coolant

    Alternator: Crompton Greaves (optional-Stamford/equivalent)

  • Brushless alternator
  • Self-excited, self-regulated
  • Class ‘H’ insulation limited to temperature rise of class H
  • Salient pole revolving field
  • Single bearing
  • Automatic voltage regulator

    Lubricating Oil system :

    Lube oil sump capacity

    50

    Oil change period (Hrs)

    500

    Oil consumption ( % of SFC)

    Less than 0.2%

    Oil filter quantity (Nos) /type

    01 / spin on type

    Recommended Oil Grade

    Greaves Maxtherm API CI4

    Oil Cooler

    Water cooled

    Acoustic enclosure – Engine alternator assembly mounted on AVM with Silencer and S.S exhaust bellow suitably optimized to meet stringent sound emission standards as laid down by MOEF / CPCB

  • Base rail with draw-out type fuel tank is provided with a drain plug, air Vent, inlet and outlet connections, level indicator, manhole etc.
  • Sub-base fuel tank with 14 hours capacity at 75% load.
  • 24 V dry, batteries with connecting leads and terminals

-90% gloss RAL9003 white pure polyester powder coated, base in black colour.

Control panel: RAL 9003 White Powder coated control panel manufactured with CRCA sheet provides:

-Water and lube oil drain outlets located on the outer surface- Leading to ease of maintenance and cleanliness.

  • – MCCB of suitable rating with short circuit protection
    • Controller which displays voltage, current, KW, PF, Frequency, KWh.
    • Indicating lamps for “Load On” and “Set Running
    • Current transformers of suitable ratings

      Cooling System :

      Cooling system is designed for max ambient temp, Deg. C at rated load

      50

      Radiator System capacity, including engine, (L)

      110 Ltr

      Water pump type

      Centrifugal, Gear Driven

    • Aluminium busbars of suitable capacity with incoming and Outgoing terminations

    • Control fuses duly wired and ferruled

Power cables: Uninyvin copper conductor cables between Alternator & Control panel inside the canopy.

Literature:-

Operation Manual

General maintenance & installation Guideline Foundation Drawing

Parts manual

Generator Controller (GCU 6120-MKII)

CONTROLER TYPE

FEATURES

DISPLAY PARAMETER

AUDIO VISUAL WARNING

SHUT DOWN WITH AUDIO VISUAL ANNUNCIATION

image_002

GCU 6120-MKII for Genset Controller

image

Compact and microprocessor based fully configurable control Unit.

Engine Oil pressure

Low Oil pressure

Low Oil Pressure

4 line LCD display

Coolant temperature

High Coolant temperature

High Coolant temperature

The unique integrated DG set controller

Fuel level indication %

Low Battery Voltage

Engine Overspeed

Incorporate both engine and alternator parameter in one console

Battery voltage

Low fuel Level

Engine uderspeed

Fully configurable digital out put

Engine rpm

High Canopy Temperature

All parameter are settable and password protected

DG set Running Hours

Low Fuel Level

AMF Ready

Generator Volts –

Phase – Neutral & Phase – Phase

Under voltage

Remote start

Generator Current

(Amps)

Over voltage

Power factor

Over frequency

KWHR

Under frequency

KW

Low coolant level

High Canopy Temperature

Optional Items:

Cooling System: Heater Kit for -20 Deg. C Operation / Heater Kit for -30 deg.Cel

Electrical Systems: Alternator Space Heater / Higher Rating Battery / Battery Charger / Battery Heater / Copper Bus Bar / Sealable kWh / Earth Fault Relay / Remote Annunciator / Remote monitoring / RTD/BTD Temperature Scanner

AMF &Synchronizing System: AMF panel / AMF with Auto-synchronization (Deep Sea / Woodward)

Open Unit (For Export) Exhaust silencer-Hospital/Residential Grade, Stainless Steel, flexible pipe.

image

Fuel System: Flexible Fuel Lines / SS fuel lines / Fuel Pressure Gauge/ fuel flow meter

Enclosed Unit:-Sound Enclosure – Super silent / External 990 Lt. Fuel Tank

Miscellaneous: Air Cleaner (Heavy Duty)/Air Cleaner Restriction Indicator Digital / Closed crankcase ventilation

image

eternal-genset-size

eternal-genset-size

Typical Enclosed GENSET Dimensions & weight

Model

Rating

Length(mm)

Width(mm)

Height(mm)

Weight(kg)

GPWII-400

400

5600

2000

2300

6200

Reviews

Only logged in customers who have purchased this product may leave a review.

Translate »