eternal-genset-greaves-cotton-500kva-ahmedabad-gujarat eternal-genset-greaves-cotton-500kva-ahmedabad-gujarat

500 KVA Diesel Generator ,

specsheet-500

Engine with direct injection, water cooled engine, 12 cylinder, V-type, 4 stroke, rated at 1500 RPM, conforming to ISO 3046 / BS 5514 has the following specifications:
– Mechanical FIP
– Electronic governor
– Turbocharger, pulse tuned exhaust manifold, stainless steel exhaust flexible connection
– Radiator Cooled, with turbocharged after cooled
-Plate type lube oil cooler
-Filter –fuel, lube oil
– Dry type replaceable paper element air cleaner
– Flywheel housing and flywheel to suit single bearing alternator
– Starting motor – Electric, battery charging alternator
– First fill lube oil and coolant

Compare
Product ID: 2594 SKU: GPWII-PII-500KVA Categories: ,

 

Diesel Generator Set Specifications Sheet- 500 kVA

 

Generator Specifications: Alternator Specification:
Voltage 380-440V
Genset Manufacturer Greaves Power Frequency 50Hz
Genset Rating Prime Power Current @ 0.8PF (Amps) 695.6
Genset Output ( KVA / KWe) 500 / 400 Type 4 Pole , Rotating field
Genset Model GPWII–500 Exciter Type Brushless (Permanent
magnet optional)
Engine rating or Max. Power at rated RPM, in 444 (604)
6, fixed.
KW (BHP)
Leads: Quantity , type 12, re connectable
Engine Model 12V14TAG23
(Optional)
Engine Type TCAC Voltage regulator Solid State
Insulation Class H ,
No. of Cylinders / Cylinder arrangement 12 / V- type
Temperature rise 125 Deg. C (Class H)
Displacement (L) 16.8
Bearing: Quantity , type 1,Sealed
Bore & Stroke (mm) 115 X 135 Coupling Flexible disc closed coupled
Voltage regulation : No load to full load 2 Phase sensing,±1%
Compression ratio 17
One step load acceptance 100% of rating
Rated RPM 1500
Unbalance load capability 25% of rated current
Governor: Type /Class of Governing Electronic/G3
Frequency regulation, No load to full load Isochronous Standard scope of supply:
Over speed trip (rpm) 1650 Engine with  direct injection, water cooled engine, 12 cylinder, V-type, 4 stroke,
rated at 1500 RPM, conforming to ISO 3046 / BS 5514 has the following
Air cleaner type  /  Qty Dry / 02
specifications:
Exhaust system – Mechanical FIP
Maximum allowable back pressure, kPa 7 – Electronic governor
– Turbocharger, pulse tuned exhaust manifold, stainless steel exhaust flexible
connection
– Radiator Cooled, with turbocharged after cooled
Engine Electrical system:
-Plate type lube oil cooler
Charging alternator Voltage / Current (DC) 24V / 44Amps -Filter –fuel, lube oil
– Dry type replaceable paper element air cleaner
Starter Motor rated voltage (DC) 24
– Flywheel housing and flywheel to suit single bearing alternator
– Starting motor – Electric, battery charging alternator
Battery Voltage (DC) / Capacity (AH) 24V, 2*180AH
– First fill lube oil and coolant
Alternator: Crompton Greaves (optional-Stamford/equivalent)
Fuel System:
– Brushless  alternator
Recommended Fuel HSD
– Self-excited, self-regulated
– Class ‘H’ insulation limited to temperature rise of class H
Fuel tank capacity ( Ltr) 990
– Salient pole revolving field
Fuel consumption – LPH at % load
– Single bearing
100% 109 – Automatic voltage regulator
75% 83 Acoustic enclosure – Engine alternator assembly mounted on AVM with
50% 66
Silencer and S.S exhaust bellow suitably optimized to meet stringent sound
25% 32.2
emission standards as laid down by MOEF / CPCB
– Base rail with draw-out type fuel tank is provided with a drain plug, air
Lubricating Oil system : Vent, inlet and outlet connections, level indicator, manhole etc.
Lube oil sump capacity 50 – Sub-base fuel tank with 11 hours capacity at 75% load.
-24 V dry, batteries with connecting leads and terminals
Oil change period (Hrs) 500 -90% gloss RAL9003 white pure polyester powder coated, base in black colour.
Oil consumption ( % of SEC) Less than 0.2% Control panel: RAL 9003 White Powder coated control panel manufactured
Oil filter quantity (Nos) /type 01 / spin on type with CRCA sheet provides:
-Water and lube oil drain outlets located on the outer surface- Leading to ease of
15W40 maintenance and cleanliness.
· – MCCB of suitable rating with short circuit protection
Recommended Oil Grade Greaves Maxtherm
– Controller which displays voltage, current, KW, PF, Frequency, KWh.
API CI4
– Indicating lamps for “Load On” and “Set Running
Oil Cooler Water cooled Current transformers of suitable ratings
Aluminium busbars of suitable capacity with incoming and
Outgoing terminations
– Control fuses duly wired and ferruled
Cooling System : Power cables: Uninyvin copper conductor cables between Alternator & Control
Cooling system is designed for max ambient 50
panel inside the canopy.
temp, Deg. C at rated load
Radiator System capacity, including engine, (L) 110 Ltr Literature:
Water pump type Centrifugal, Gear Driven Operation Manual
General maintenance & installation Guideline
Foundation Drawing
Parts manual

 

 

 

Generator Controller (GCU 6120-MKII)

 

CONTROLER TYPE FEATURES DISPLAY PARAMETER AUDIO VISUAL WARNING SHUT DOWN WITH AUDIO
VISUAL ANNUNCIATION
Compact and
microprocessor based fully Engine Oil pressure Low Oil pressure Low Oil Pressure
configurable control Unit.
GCU 6120-MKII for Genset
High Coolant
Controller 4 line LCD display Coolant temperature High Coolant temperature
temperature
The unique integrated DG Fuel level indication % Low Battery Voltage Engine Overspeed
set controller
Incorporate both engine
and alternator parameter Battery voltage Low fuel Level Engine uderspeed
in one console
Fully configurable digital
out put Engine rpm High canopy temperature
All parameter are settable DG set Running Hours Low fuel level
and password protected
Generator Volts –
AMF Ready Phase – Neutral & Under voltage
Phase – Phase
Generator Current Over voltage
Remote start (Amps)
Power factor Over frequency
KWHR Under frequency
KW Low coolant level
High Canopy Temperature

 

 

 

Optional Items:

 

Cooling System: Heater Kit for -20 Deg. C Operation / Heater Kit for -30 deg.Cel

 

Electrical Systems: Alternator Space Heater / Higher Rating Battery / Battery Charger / Battery Heater / Copper Bus Bar / Sealable kWh / Earth Fault Relay / Remote Annunciator / Remote monitoring / RTD/BTD Temperature Scanner

 

AMF &Synchronizing System: AMF panel / AMF with Auto-synchronization (Deep Sea / Woodward)

 

Open Unit (For Export) Exhaust silencer-Hospital/Residential Grade, Stainless Steel, flexible pipe.

 

Fuel System: Flexible Fuel Lines / SS fuel lines / Fuel Pressure Gauge/fuel Flow Meter

 

Enclosed Unit:-Sound Enclosure – Super silent / External 990 Lt. Fuel Tank

 

Miscellaneous: Air Cleaner (Heavy Duty)/Air Cleaner Restriction Indicator Digital / Closed crankcase ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Typical Enclosed GENSET Dimensions & weight

 

Model Rating Length(mm) Width(mm) Height(mm) Weight(kg)
GPWII-500 500 5600 2000 2300 6700
Weight 6700 kg
Dimensions 5600 x 200 x 2300 mm
Genset Output ( KVA / KWe)

400/500

Engine rating or Max. Power at rated RPM, in

444 (604)

Reviews